Steam is commonly used for process heating. Typically, saturated steam is produced in shell and tube (fire tube) boilers. Its advantages are obvious: the heat content is high, and temperature can be regulated by controlling pressure. When looking at the properties of saturated steam, it can be seen exactly at the border line between liquid water and gaseous steam (vapour).
When dry saturated steam passes on its energy to a process, its “latent” energy is released. This energy can be found in steam tables as enthalpy (hfg). Whilst this energy is released, the steam becomes wetter, i.e. its dryness fraction (x) is reduced from 1 to 0. What doesn’t change, however, is the combination of pressure and temperature during this process. This means that ideally steam enters a heat exchanger at 3 bar g and +144°C and condensate can be found at the exit at the same pressure and temperature — but the steam has lost 2138 kJ/kg of latent heat (hf). The problem now is: if both liquid and steam, and any state in between, can exist at the same pressure and temperature, it is impossible to determine the dryness fraction by just measuring pressure and temperature. Therefore, today there is no solution available to easily determine if water is present in the steam line or not.
Fig.1: Mollier diagram for water. Example: Heating liquid water from 20°C (A) to 100°C (B) requires about 4.2 kJ/kg× K of energy. To convert the water (B) to steam (C) at 100°C and 1.013 bar abs., 2255 kJ/kg are required (hf). During this process, the dryness (x-factor) is increased from 0 to 1.
Fig. 2: The dryness of steam is defined by the “x-factor”. If x = 0, water is fully saturated. If x = 1, there is dry saturated steam. If x = 0.8, 80% of the mass of water is in a gaseous state and 20% in a liquid state.
Heat losses in steam piping, e.g. because of lack of isolation, will lead to a reduced dryness fraction. This wet steam can lead to the following problems:
If the wet steam is a result of carry-over from the boiler itself, stress corrosion cracking may result. Wet steam, however, is also an issue at the point of end-use. If the condensate trap at the outlet of a boiler does not work, the heat exchanger may drown, thus reducing the heat transfer efficiency drastically.
Fig. 3: Drowned heat exchanger (left) resulting in poor steam quality upstream.
Another potential problem lies in underperforming separator equipment for producing saturated dry steam which may also result in wet steam and reduced efficiency. All these examples show: wet steam can occur anywhere in a process heating system — even if it is assumed that the steam has been superheated! Over the recent years, more and more customers have expressed their concerns about these issues to Endress+Hauser. The most asked question was “How can I find out if the steam is wet?”
The above repeated questions led Endress+Hauser to invest in a steam rig together with the University of Applied Sciences and Arts/Northwestern Switzerland in Windisch. This steam rig allowed us to create steam at different dryness levels and to investigate the effect of moisture in the steam on our new Proline vortex flowmeters. Dryness fractions between 80 and 100% can be generated for line sizes DN 25 (1″), DN 40 (1½″), DN 50 (2″), DN 80 (3″) and DN 100 (4″). Steam pressures of up to 10 bar g can be achieved. The wet steam was created in different ways by injecting water as a “river flow”, “mist flow” and by means of a cooling pipe. In all three cases, the investigations showed that in horizontal pipelines increasingly wet steam first formed “channel flow” at the bottom of the pipeline and then “smeared” up along the pipeline walls, independent of how the liquid water was injected.
Fig. 4: Steam research facility from Endress+Hauser and the University of Applied Sciences and Arts/Northwestern Switzerland in Windisch.
Fig. 5: Steam at different dryness fractions (from left to right: 100%, 95%, 90%). A dryness fraction of 90% means that 10% (mass) of the total water content is present as water containing much less energy than gaseous steam. Therefore, 10% less energy is available!
Further research showed that when installing a Prowirl 200 vortex flowmeter into a horizontal pipeline with the electronics head mounted in the “6 o’clock position”, the “river flow” mentioned above had an influence on the sensor signal. Its kurtosis, i.e. the steepness of the amplitude, changes because of the changing state of the fluid. This simple fact has an exciting result: the meter can “decide” if the steam present in the pipe is dry or wet. The device even allows a value to be entered for the steam quality, below which the device will give a “steam quality” warning.
Fig. 6: As soon as “wet steam” is in the pipe, Prowirl 200 issues an alarm message.
Endress+Hauser has been producing vortex flowmeters for almost 30 years and has gained experience in more than 300,000 applications; more than half of these are in steam. About 10 years ago, the Proline Prowirl 73 was introduced, a multivariable two-wire vortex flowmeter. Even today, Prowirl — today’s generation is the Prowirl 200 — is the only multivariable vortex flowmeter family worldwide that combines several benefits:
The multivariable Prowirl vortex flowmeter is now optionally available with “wet steam detection”. We have already received positive feedback from several customers that this feature will strengthen Prowirl’s position as the best solution available for steam measurement in process heating systems — increasing both safety and efficiency.
The HRS Unicus series is a scalable solution that enables heat transfer in sensitive or viscous...
For over thirty-five years, Citect delivered innovative, reliable, and flexible SCADA software...
The need for an all-in-one solution for automation tasks comes from a single source, SEW...
Food traceability about to get fruity with Australian Table Grapes
Increase safety and improve efficiency by detecting wet steam
Top 10 considerations when moving to heat pumps
2021 Winner — excellence in refrigeration
The 6x: the new radar level sensor
The 6x: the new radar level sensory
Tailor-made heat pump and thermal energy storage for food and beverage sector
APCO announces recycled materials pledge
Wastewater pump for Junee Prime Lamb
Aurecon appoints new lead for its climate transition advisory unit
UNSW to lead decarbonisation hub
Urban Utilities commits to net zero by 2032
Frozen testicular tissue deemed viable after two decades
Pictured: the black hole at the heart of our galaxy
CEPI consortium to develop 'variant-proof' COVID vaccine
50:50 chance of reaching 1.5°C threshold in next five years
Magnetic therapy enhances chemo treatment of breast cancer
Reduce preventable medical errors with Zebra Workforce Connect
Raw meat parasite linked to common eye disease
Alarming rise in esophageal cancer cases in middle-aged adults: US study
COPD management: trial to address deficiencies in primary care
Two-thirds of people unaware of Home Medicines Review — survey
Westwick-Farrow Media Locked Bag 2226 North Ryde BC NSW 1670 ABN: 22 152 305 336 www.wfmedia.com.au Email Us
Our food industry media channels - What’s New in Food Technology & Manufacturing magazine and the Food Processing website - provide busy food manufacturing, packaging and design professionals with an easy-to-use, readily available source of information that is crucial to gaining valuable industry insight. Members have access to thousands of informative items across a range of media channels.
Membership is FREE to qualified industry professionals across Australia.